FOR DIVERSE APPLICATIONS
Rectangular fire damper for the isolation of duct penetrations between fire compartments, for a variety of installation situations, available in many different sizes and constructions
Nominal sizes 200 × 200 – 1500 × 800 mm, in increments of 1 mm
Low differential pressure and sound power level
Explosion-proof construction (ATEX) as an option
Can also be used as an air transfer damper
Optional stainless steel casing or powder-coated casing for increased corrosion protection
Integration into the central BMS with TROXNETCOM
Universal installation options
Optional equipment and accessories
Electric actuator 24 V/230 V
Release temperature 72/95 °C
Duct smoke detector RM-O-3-D
Rectangular or square fire dampers for the isolation of duct penetrations between fire compartments.Tested for fire resistance properties to EN 1366-2, with CE marking and declaration of performance according to the Construction Products Regulation. Ready-for-operation unit, which includes a fire- resistant damper blade and a release mechanism. For mortar-based installation and dry mortarless installation into solid walls and ceiling slabs, mortar-based installation into non-load-bearing solid walls with flexible ceiling joint, mortar-based and dry mortarless installation into lightweight partition walls, lightweight partition walls with cladding on both sides, lightweight fire walls and lightweight shaft walls. For dry mortarless installation on the face of solid walls, adjacent to solid walls, remote from solid walls and remote from solid ceiling slabs.