For early detection of flaming fires caused by the combustion of liquid and solid matter, as well as smoldering fires. For early and reliable fire detection in environments with deceptive phenomena.
Works according to the scattered-light principle with two sensors, optical forward and backward scattering. Opto-electronic sampling chamber blocks disturbing extraneous light but optimally detects both dark and light smoke particles. Two additional heat sensors increase the fire detector’s immunity to deceptive phenomena. Software can be set to multi-sensor smoke detector, smoke detector or heat detector. Selectable detection behavior thanks to application-specific ASA parameter sets.
Can be used as an addressable or collective device.
The base must be ordered separately.
Also available in different colors.
Standard
EN 54-5 , EN 54-7 , EN 54-17 , CEA 4021
Protection category
IP43; IP44 with base attachment
Operating voltage
FDnet DC 12…33 V
Operating temperature
-30…75 °C
Storage temperature
-30...+75 °C
Quiescent current
200...280 μA
Ext. alarm indicator
2 without sounder base 1 with sounder base
System compatibility
FDnet -> FS20, AlgoRex, SIGMASYS
Communication protocol
FDnet
Relative humidity
≤95 % rel.
Permissible air speed
1…20 m/s
Dimensions (Ø x H)
100 x 46 mm
Color
Pure white, ~RAL 9010
Accessories
FDBZ293 Detector locking device , FDZ291 Detector dust cap