For the detection of flaming fires caused by the combustion of liquid and solid matters, as well as smoldering fires. For reliable fire detection in environments with deceptive phenomena.
Works according to the scattered-light principle with an optical forward scattering sensor. An additional heat sensor increases the fire detector’s immunity to deceptive phenomena. Selectable detection behavior by different parameter sets. Immunity against transient false alarm causes.
The base must be ordered separately.
Standard
CEA 4021 , EN 54-7 , EN 54-17
Protection category
IP40; IP42 with detector base seal
Operating voltage
DC 12…33 V
Operating temperature
-10…55 °C
Storage temperature
-30...+70 °C
Quiescent current
~230 μA
Ext. alarm indicator
2
System compatibility
C-NET -> FS720
Communication protocol
C-NET
Relative humidity
≤95 % rel.
Permissible air speed
5 m/s
Color
Pure white, ~RAL 9010
Accessories
LP720 Detector locking device