Operate direct driven zone dampers used to control air flow in ducts specifically to address two or three-position domestic and light commercial barrel damper applications.
For shaft dia 8...15 mm, square 6...11 mm, min. shaft length 20 mm
With housing made of plastic and 0.9 m connecting cable
Torque
2 Nm
Air damper area
0.3 m²
Angular rotation
90°
Power consumption
2.2 VA, 1.2 W
Positioning time
30 s
Cable length
0.9 m
Positioning signal
Open-close / three-position
Degree of protection
IP54
Ambient temperature, operation
-32...55 °C
Dimensions (W x H x D)
73 x 122 x 63 mm
Operating voltage
AC 24 V, DC 24…48 V
Auxiliary switch
2
Electric motor-driven rotary actuators for open-close, three-position
and modulating control
● 2 Nm nominal torque
● Operating voltage AC 24 V ~ / DC 24…48 V ⎓ or AC 100…240 V ~
● Prewired with 0.9 m connecting cable
● Gear train disengagement button for manual adjustment
● Position indication
● Auxiliary switches for auxiliary functions
The rotary actuator drives the damper to the desired operating position after connecting the
operating voltage.
● Brushless, robust DC motors ensure reliable operation regardless of load.
● The rotary actuators do not require an end position switch, are overload proof, and remain
in place upon reaching the end stop.
● The gears are maintenance free and low noise.
● Simple and reliable shaft integration.
● Mounting bracket included.