Inadequate protection around service penetrations can put buildings at risk of fire spread. The ROCKWOOL Firestop Compound offers a reliable solution to effectively re-instate compartmentation within fire rated walls and floors, offering the property critical fire stopping protection. When used in floors, Firestop compound provides a load-bearing seal.
The installation of ROCKWOOL’s Firestop Compound provides up to 6 hours fire protection to provide a fire resisting seal in masonry fire rated walls and floors. As independent tests have shown, when reinforced, Firestop Compound offers masonry and concrete walls or concrete floors with up to 360mins* protection for both integrity and insulation, and when un-reinforced, it offers up to 240mins* protection.
Existing compound installations can be easily drilled to allow the provision of additional or replacement services which can subsequently be re-sealed.
As part of the comprehensive FIREPRO® range of fire protection products, the Firestop Compound is an ideal solution for cable pipe and duct penetrations. The ROCKWOOL Firestop product is easy to use as it’s a specially formulated gypsum based compound, which is mixed with water to be trowelled or poured around service penetrations.*
*Plastic pipework must be protected with either ROCKWOOL Firestop Pipe Collars or Intumescent Pipe Wraps. (See separate product information)
Accreditations
Tested to BS476: Part 20 1987
IFC approved
Load bearing – provides load bearing fire seals for light foot traffic. With openings larger than 750 x 750mm, a clear area needs to be reinforced (see technical datasheet for details).