Overview
Filtering ceilings developed by MP3 are able to provide necessary requirements by creating a unidirectional air flow at the critical speed. They also allow for easy maintenance for the wellbeing of for the surgical team.
Technical data
AISI 304 stainless steel construction
Plenum same for all filters
Integration in the ceilings with perfect seiling with 600x600 tiles
HEPA filter elements (≥ 99.995% efficiency)
Finishing designed to prevent the accumulation of pollutants and ensure integration with other technical elements
Pressure gauges holes
Sample holes for leakage testing according to EN 14644-3