CE marking-compliant in accordance with EN 15650.
Products tested to beyond European requirements under a minimum pressure of 500 Pa.
Fire class ratings obtained on main supports, assembly in all positions (blade horizontal and vertical) and in both fire directions.
Flush-mounted range available in 2 versions:
FdP: very low pressure losses, used to minimise pressure loss created by the passing airflow.
EM: minimum dimensions to adapt to confined spaces.
Quick and economical to install using traditional mortar.
Motor available in 24 V or 230 V versions.
Consists of 2 metal sleeves on both sides of an assembly of refractory material.
FdP flush-mounted range: available in circular (Ø 100 to 315 mm) and rectangular versions (200×200 to 800×600 mm).
EM flush-mounted range: available in circular ( Ø 100 to 1000 mm) and rectangular versions (200×200 to 1500×600 or 1200×900 mm).
BLF motor mechanism (circular and rectangular dampers, small and medium dimensions).
BF motor mechanism (large and very large rectangular dampers).
Motor available in 24 V or 230 V versions.
All mechanisms are equipped with:
FC/DC end of travel / start of travel contacts.
72 °C trip fuse.
DESCRIPTION
• All ISONE+ fire dampers can house the BF/BLF
mechanism equipped with its 72° fuse (BAE 72),
and a closed (FC) contact and open (DC) contact
FIRE PROTECTION RATING EN 15650
• EI 120 S – 500 Pa in 150 mm concrete slab and
150 mm cellular concrete.
• EI 90 S Pa on 70mm plaster blocks, EI 120 S on
100mm plaster bocks.
INSTALLATION
• Identical to ISONE with an Aldes mechanism
FIRE PROTECTION RATING EN 15650
• EI 120 S – 500 Pa in 150 mm concrete slab and 150 mm
cellular concrete.